| 
         AIPHONE Troubleshooting 
This page contains answers to common questions handled by     our Technical Support staff, along with some tips and tricks that we have found useful and     presented here as questions. 
If your question is not answered here you may submit a     question directly to Technical     Support. 
Please click on the system that you are     working with:  
C-123L/A, C-123LW        Trouble Shooting       Flowcharts:        C-123L, C-123LW 
1. C-123L system has a buzz or hum. 
Wire was run too close to AC voltage or fluorescent lights.         Shielded wire is recommended. If shielded wire was run, connect one end of the shield to         an earth ground. 
Refer to C-123L         Instructions. 
 
 
2. Call tone is too loud.  
1. Check for proper voltage. C-123L/A is a 6V DC system.  
Refer to C-123L/A         Instructions. 
2. There is no call tone adjustment on the C-ML/A. If         voltage is right, the master can be modified to lower call tone. Contact Aiphone         Technical Support for modification information.  
 
 
3. Newly installed C-123LW, feedback when either     master tries to communicate with the door. 
Is there only one power supply for both masters?         C-123LW requires two SKK-620’s, one per master (or 4 “C” batteries in each         master.) 
Refer to C-123LW Instructions. 
 
 
4. Newly installed C-123LW, when one master tries     to communicate with the door a chime tone is heard at the other master. 
Dual Adapter Kit (DAK-2S) is not installed, or installed         backwards. 
Refer to C-123LW Instructions. 
 
 
5. Newly installed unit is totally dead. 
Make sure unit has 6V DC (12V DC will severely damage the         unit).          Make sure power connections are on + and – terminals. (Check to make sure the wires on the         – and 1 terminals are not reversed.)  
Refer to C-123L         Instructions. 
 
 
Back to top  
LEF System      Trouble Shooting     Flowchart:      Master to Audio Only Sub       
1. New LEF with All Call adapter has more than one     light coming on when subs call in. 
1. Check to see if “E” & “-”         wires are shorted together anywhere in the system.   
2. Capacitors (NP-25V) are required between master and All         Call adapter, in series with each station number terminal assigned to an indoor sub         station.   
Refer to BGR-10A         Instructions. Refer to BG-10C Instructions. Refer         to LEF-C Instructions. Refer to LEF Instructions. 
 
 
2. New LEF system has buzz or hum. 
Master(s) is too close to AC voltage or dimmer switches.         Shielded wire is recommended. If shielded wire was run, tie all of the shields together         and ground one end to an earth ground. 
Wire between master stations must be in one         jacketed cable. If multiple cables were used, make sure all station number wires and the E wire are         in the same jacketed cable.  
Refer to LEF-C         Instructions. Refer to LEF Instructions 
 
 
3. New LEF system has more than one light coming on     when subs call in.  
1. In a multiple master system, make sure that the “E” & “-” are not shorted together.  
Refer to LEF-C         Instructions. Refer to LEF Instructions 
2. Possible power surged units, send in for repair. 
 
 
4. Existing LEF system has more than one light     coming on when subs call in. 
Possible power surged units, send in for repair. 
 
 
5. LEF one master system, communication with the     sub is fine, but no call tone (or call tone but no communication or a combination of both     at different subs).  
If running 2 conductors to sub stations: Jumper between         “E” & “-” has been removed and must be reinstalled on all units,         including master station.  
Refer to LEF-C         Instructions. Refer to LEF Instructions 
 
 
6. LEF system, “Occupied” light always     on.  
A station in the system is in the “ON” position,         the “R” wire is shorted, or a unit in the system is damaged. 
Refer to LEF-C         Instructions. Refer to LEF Instructions 
 
 
7. LEF system, no communication between masters. 
Improper connection of the “C” terminal.         (“C” Stands for “call”, not “common”). Check wiring         connections between master stations to make sure the wire on the “C” terminal is         wired properly. “C” of master 1 connects to 1 of all other masters.         “C” of master 2 connects to 2 of all other masters, etc.  
Refer to LEF-C         Instructions. Refer to LEF Instructions. 
 
 
8. LEF/BGR, no audio or music but has lights &     shows display. 
PS-1225UL (or PS-12C) and PS-2410A          (or PS-24C) power supplies might be swapped. 12V DC         power goes to LEF, 24V DC goes to BGR-10A. 
Refer to BGR-10A         Instructions, BG-10C Instructions, LEF-C Instructions or LEF         Instructions. 
 
 
9. LEF/BGR, music gets louder when selecting a     station from a master. 
“R” or the “12V -” are not connected         from the LEF to the BGR-10A.  
Refer to BGR-10A         Instructions, BG-10C Instructions, LEF-C Instructions or LEF         Instructions. 
 
 
10. LEF System, “All Call” isn’t     working. 
1. All call requires additional equipment (BGR-10A with         PS-2410A, or BG-10C with PS-1225UL).  
Refer to BGR-10A               Instructions, BG-10C               Instructions, LEF-C               Instructions or LEF           Instructions. 
2. If additional equipment is present, check for proper         connection of P1, P2, and P3 terminals from the master stations to the BG-10C or BGR-10A.  
Refer to BGR-10A         Instructions or BG-10C Instructions. 
 
 
11. LEF system with All Call/music, subs     continuously call in if music is on or all call is attempted (LE-A/AN, LE-B/BN, LE-D/DA     sub stations only). 
The system requires one NP-25V capacitor for each sub         station. Install capacitor in series on all sub station number terminals between the LEF         master and All Call/Music adapter. 
Refer to BGR-10A               Instructions, BG-10C               Instructions, LEF-C               Instructions or LEF           Instructions. 
 
 
12. LEF System with BGR-10A/BG-10C door station     does not chime when call button is pressed.  
Check for proper connection of the DA/DB/DC terminals and         the 12V DC “-” between BGR-10A/BG-10C and LEF master. Number wire (1) from door         station must be connected to DA, DB, or DC terminal. Negative of LEF must be connected to         – of BGR-10A. “E” is common communication. Chime tone is generated by a         momentary closure between 1 & – of door station, activating chime by shorting DA to –         in BGR-10A (BG-10C).  
Refer to BGR-10A               Instructions, BG-10C               Instructions, LEF-C               Instructions or LEF           Instructions. 
 
 
13. LEF System with BGR-10A/BG-10C door chimes when     call button is pressed, however the electronic call tone is heard as well.  
Door station must tie to the BGR-10A/BG-10C first. Also,         SW-5 on the back of the main PC board needs to be in the “A” position (on all         LEF series masters). LEF-C masters come in the “A” position from the factory.         LEF surface mount units come in “B” position, and must be changed to         “A” when used with BG-10C. 
Refer to BGR-10A               Instructions, BG-10C               Instructions, LEF-C               Instructions or LEF           Instructions. 
 
 
14. LEF System, the door release doesn’t     function. 
The LEF requires an RY-PA relay for each door being         released. Two black wires are input side, requiring 12V DC to activate relay. Two yellow         wires provide a normally open dry closure when the relay is activated.  
Refer to LEF Instructions. 
 
 
15. LEF/MY system has a     buzz or hum. 
1. Connect “G” terminal on the PS-1820UL         power         supply to an earth ground. 
         2. Make sure that the MONITOR is on the left-hand side of the LEF intercom when facing the         units.  
         3. Make sure the video wiring (18AWG, 6 conductor) is run in a separate jacketed cable         from the intercom wires, and that the intercom wiring is not run directly behind or near         the video monitor.  
Refer to MYW-P3L         Instructions, MYW-P1L Instructions, LEF-C Instructions or LEF         Instructions. 
 
 
16. LEF/MY system has a buzz or hum when the     monitor is on. 
Monitor has to be on the left side of the LEF master.         (it         cannot be on the right.) Also, ground the PS-1820UL terminal to the         PS-1225UL. Refer to         #15. 
 
 
17. LEF/ MY system, proper door camera comes on     when the call button is pressed, however all video and communication is lost when the     station is selected. 
1. “K” terminals are improperly connected or not         connected at all.           Video door stations 1, 2, and 3 correspond to DA/KA, DB/KB, and DC/KC terminals         accordingly. E.g. If door #1 is on channel 10, K10 of master station must be connected to         KA of MYW-P3L. Likewise for other stations.  
Refer to MYW-P3L               Instructions, MYW-P1L               Instructions, LEF-C               Instructions or LEF           Instructions. 
 
 
18. LEF/ MY system, proper door camera comes on     when the call button is pressed, however there is no control of the pan and tilt     functions. 
1. Wire gauge is too thin or power supply is too far         away.  Make sure power supply is within 16′ of the adaptor or         monitor and is connected using 18 AWG wire. 
2. Take affected unit to “working” location or to         the MYW Adapter and test.  
Refer to MYW-P3L               Instructions, MYW-P1L               Instructions, LEF-C               Instructions or LEF           Instructions. 
 
 
19. Monitor does not turn on when door station call     button is pressed. 
1. Take a voltage reading between U1 and -.  It should         be roughly 18V DC. Check connection between MYW adapter and MYH monitor to make sure +, -,         U1, and U2 terminals are connected properly.  
2. Short U2 to – at monitor, and the monitor should turn         on.   
3. Short U2 to – at the previous monitor or MYW adapter to         isolate the problem to wiring or equipment. 
Refer to MYW-P3L               Instructions, MYW-P1L               Instructions, LEF-C               Instructions or LEF           Instructions. 
 
 
20. LEF/ MY system, no call tone from camera.        
Perform jumper test at LEF Master (short station number to         “-“).  If call tone is heard, repeat jumper test on the appropriate D         terminal (DA, DB, DC) and “-” at the MYW Adapter.  If call tone is heard,         perform jumper test at appropriate A1, A2 terminals.  If call tone is heard, take         wires off of camera and short together. If that works, then the call button in the camera         is malfunctioning. 
 
 
Use jumper tests as described to isolate problem to         specific equipment or wire.  
Refer to MYW-P3L               Instructions, MYW-P1L               Instructions, LEF-C               Instructions or LEF           Instructions. 
 
 
Back to top  
LEM System      Trouble Shooting Flowchart:      LEM/LEM-1DL 
1. LEM system has a buzz or hum.  
Wire was run too close to AC voltage or fluorescent lights.         Shielded wire is recommended. If shielded wire was run, connect one end of the shield to         an earth ground.  
Refer to LEM         Instructions. 
 
 
2. LEM-1DL system has a buzz or hum.  
1. Wire was run too close to AC voltage or fluorescent         lights. Shielded wire is recommended. If shielded wire was run, connect one end of the         shield to an earth ground.  
Refer to LEM-1DL         Instructions. 
2. Make sure that the wires from the power supply are not         run in the same cable as the door station wires. If they are, move them to a separate         cable.  
Refer to LEM-1DL         Instructions. 
 
 
3. Newly installed LEM-1DL is completely dead. 
Wrong power supply (LEM-1DL requires the PT-1210N). Voltage         for the LEM-1DL can be 12-16V AC or 12-24V DC. 
Refer to LEM-1DL           Instructions. 
 
 
4. New installation, communication with the sub is     fine, but no call tone (or call tone but no communication). 
Jumper between “E” and “-” terminals at         the door station has been removed and must be reinstalled.  
Refer to LEM         Instructions or LEM-1DL Instructions. 
 
 
5. Dual LEM system, feedback when either master     tries to communicate with the door. 
Is there only one power supply on the system? Each LEM-1DL         requires its own PT-1210N.          Each LEM1- or LEM-3 requires its own SKK-620.  
Refer to DAK-2S Instructions. 
 
 
6. Dual LEM system, when one master tries to     communicate with the door a call tone is heard at the other master. 
Dual Adapter Kit (DAK-2S) is not installed or is installed         backwards. (Use one component module per master station, bare leg connected to         “1” terminal.) 
Refer to DAK-2S Instructions. 
 
 
Back to top  
MC-60/4 System 
1. Intermixed with MC-3 system, VOX circuit on the     MC-60/4 “chatters ” or clips first/last word of communication.  
Improper power supply (When MC-60/4’s are installed         the PS-2420UL must be used). 
 
 
2. No communication on a specific line.  
Check for proper connection of :          Line 1 (red) – Terminal 4          Line 2 (green) – Terminal 3          Line 3 (yellow) – Terminal 6          Line 4 (orange) – Terminal 7           Power: 1 = +, 5 = Neg.           Paging: Terminal 2 
Refer to MC-60/4         Instructions. 
 
 
3. No Paging. 
1. Check for proper connection of terminal #2. Voltage         between 2 and 5 should be approx. 10V DC to trigger pretone and paging.  
Refer to MC-60/4         Instructions. 
2.Check for proper paging adapter (MC-60/4 requires either         the MC-A/A adapter or the use of a PG-C series amplifier).  
Refer to MC-A/A         Instructions.  
3. If a PG-C amplifier is used, check the settings of         switches 7 and 8 (7 should be on, 8 should be off). 
Refer to PG-C Instructions. 
 
 
4. Some units on one run are completely     “dead” while others are fine. 
Check for proper connections of terminals 1 and 5 (1 is         positive, 5 is negative). Also refer to questions #2 and #3.  
Refer to MC-60/4         Instructions. 
 
 
5. Feedback while paging. 
Overhead speakers are located too close to the handset         initiating the page. Either turn down the amplifier until the feedback goes away, or         modify the units for local speaker cut-out. 
Contact Aiphone         Technical Support for modification information.  
 
 
6. MC-60/4 system with the PG-C series amplifier,     music and paging are fine but there is no page pre-tone at all.  
The #6 dip switch on the PG-C series amplifier must be         “on” for any pre-tone to be heard, refer to #7.  
Refer to PG-C Instructions. 
 
 
7. Music and paging are fine but paging pre-tone is     too loud or too quiet. 
Pre-tone volume is adjusted separately from paging /music         volume. If the system includes a PG-C series amplifier, the pre-tone control is located         with the Bass/ Treble controls. If the system is using an MC-A/A, the pre-tone control is         on the bottom of the MC-A/A.  
Refer to PG-C Instructions         or MC-A/A Instructions. 
 
 
Back to top  
MY Video 
1. MY camera continues panning or tilting after the     PanTilt button is released.  
Power Supply or master monitor needs to be connected to an         earth ground. Connect “G” terminal on PS-1820UL or SG terminal on MY-1CD monitor to         ground.  
 
 
2. Picture on monitor rolls. 
Wire gauge is too thin, improper power supply, or power         supply is too far away from monitor. Power supply must be within 16′ of monitor.  
 
 
3. Monitor fails to bring up the camera. 
Not enough power at the monitor, power supply is too far         away, or there are too many monitors on one power supply (three monitors maximum on one         PS-1820UL). 
 
 
4. Monitor comes on but picture has a     “ghost” image or is distorted.  
Are there extra conductors in the cable going out to the         camera? Terminate extra pairs of wires by connecting a 120 ohm resistor on each end of         each extra pair of wires, or double up on the wires to create a single wire out of each         pair. 
 
 
5. Camera calls in continuously without button     being pushed at camera. 
The voltage going out to the camera is too low. The voltage         at the camera should be approximately 8V DC in standby, 6.5V DC when calling in, and 14V         DC when in communication. If the voltage is below that, it will cause the door station to         call in. Be sure that the power supply is the correct wattage and amperage, and is within         16 feet of the main monitor or adapter. Another possible cause is if the power supply is         not grounded. Connect the GND terminal of the power supply to an earth ground.  
 
 
Back to top  
NEM System 
1. Sub station does not call in, but there is     communication. 
Number and “E” wires are reversed. 
Refer to the NEM         Instructions. 
 
 
2. Sub station call is momentary, but does not     latch.  
1. Jumper clip/wire at sub is missing (On the NA-A/AN, the         jumper clip is between the “D” and “E” terminals. On the NA-NE and the         NB-L, the “Green” and “Black” wires must be tied together, going to         the “E” of the master). 
2. If an LE- series sub station is being used without         adding the PC-359B, the call will not latch. Add one PC-359B latching circuit board at         each sub station. Contact Technical Support for         modification instructions.   
Refer to the NEM         Instructions or PC-359B Instructions.  
 
 
3. Existing NEM system has more than one light     coming on when subs call in. 
1. Make sure the station numbers on the master station or         the number wires from the sub stations are not shorted together.           2. Other cause is possible power surge at the master. Send in for repair. 
 
 
4. NEM system has buzz or hum. 
Wire was run too close to AC voltage or fluorescent lights.         Shielded wire is recommended. If shielded wire was run, tie all the shields together and         connect one end to an earth ground.  Connect the negative of the power supply to an         earth ground. (If noise is still there, try connecting ground to the E terminal of the         master station.) 
Refer to the NEM         Instructions. 
 
 
5. Constant call tone and LED from “SPEAKER     ONLY” locations. 
Speaker-only stations (SP-20N) require an NP-25V capacitor         in series with the leg of each speaker that is connected to the number terminal on the NEM         master. (This is only used when the speaker location does not have a call button to place         a call to the master station.) 
 
 
6. All Call is garbled or distorted. 
Check for proper power supply.  The NEM-10/10A and the         NEM-20/20A require the PS-2410A, the NEM-30/30A and the NEM 40/40A require the         PS-2420UL. If         add-on selectors are included in the system, each one will require its own power supply.         The N-20AS requires a PS-2410A and the N-40AS requires a PS-2420UL.  
Refer to the NEM         Instructions or N-AS Instructions. 
 
 
Back to top  
RAX/RCX System 
1. Station is “dead” or malfunctioning. 
Swap unit with a station that is known to work. If the         problem follows that station, send the unit in for repair. If the problem stays in the         location, swap the subscriber card associated with that station with a subscriber card         that is known to work. If problem follows the subscriber card, send in that card for         repair. If the problem stays within location, the problem is in the wiring.  
Refer to RAX Instructions,         RCX Instructions 
 
 
2. Feedback while paging. 
Overhead speakers are located too close to the master         initiating the page. Turn down the amplifier until feedback goes away or move the speaker         (The RA-A & RA-B have omni-directional microphones that are more susceptible to this         type of problem. Using the RA-A in the handset mode or switching to an RA-D may reduce the         problem). 
 
 
3. System with the PG-C series amplifier, music and     paging are fine but there is no paging pre-tone at all. 
The #6 dip switch on the PG-C series amplifier must be         “on” for any pre-tone to be heard. Refer to #4.  
Refer to the PG-C         Instructions. 
 
 
4. Music and paging are fine but paging pre-tone is     too loud or too quiet. 
Pre-tone volume is adjusted separately from paging/music         volume. If the system includes a PG-C amplifier, the         pre-tone control is located with the Bass/Treble controls. If a system is using the         MC-A/A, the pre-tone volume control is located on the bottom of the MC-A/A.  
Refer to the MC-A/A         Instructions. 
 
 
Back to top  
TD-H System 
1. No communication between handsets.  
Improper connection of the “C” terminal         (“C” stands for “call”, not “common”). Connect the         “C” terminal of a phone to the designated number terminal on another phone.         (e.g. “C” of phone #1 connects to “1” terminal of other phones;         “C” terminal of phone #2 connects to “2” terminal of all other phones,         etc.) 
Refer to TD-H         Instructions. 
 
 
2. Feedback while paging. 
Overhead speakers are located too close to the master         initiating the page. Turn down the amplifier until feedback goes away, move the speaker,         or obtain an RY-SP local speaker cut-out relay and         install according to the instructions provided. 
 
 
3. No paging.  
Check for proper paging adapter (TD-H requires either the         PD-1 or PD-2 adapter, or the use of a PG-C series amplifier). If a PG-C amp is used, check         the setting of switches 7&8 (For the PD-1; 7 is on, 8 is off. For PD-2; 7 is off, 8 is         on).  
Refer to PD-1 Instructions,         PD-2 Instructions or PG-C         Instructions. 
 
 
4. System with PG-C series amplifier, music and     paging are fine but there is no paging pre-tone at all. 
The #6 dip-switch on the PG-C         amplifier must be “on” for any pre-tone to be heard. Refer to #5. 
 
 
5. Music and paging are fine but paging pre-tone is     too loud or too quiet. 
Pre-tone volume is adjusted separately from paging / music         volume. If the system includes a PG-C amplifier, the         pre-tone control is located with the Bass/Treble controls. If the system is using a PD-1 or PD-2, the         pre-tone volume control is located on the bottom of the paging adapter. 
 
 
6. Door station calls in, but there is no     communication.  
A DE-UR door station adapter is required for each door         station being connected. Only IF/IE door stations may be used with the TD-H system. Check         for proper connection of the “C” terminal between the DE-UR and the TD-H         handsets.  
Refer to the DE-UR         Instructions. 
 
 
7. Door station calls in and communicates, but the     door release does not work. 
For the door release to function, communication must first         be established with the door station.  Then press the “page” button in the         handset. Door strike must have its own power source, and be connected to the EL, EL         terminals in the DE-UR. 
Refer to the DE-UR         Instructions. 
 
 
8. Door station volume is too low.  
Only IE/IF door stations may be used with the TD-H system.         Check for proper connection of the door station to the DE-UR and also the “C”         terminal between the DE-UR and the TD-H handsets. The volume to the door station is         inherently low, due to the fact that the door station contains a speaker and microphone.         The DE-UR can be modified to raise the volume at the door station, but the resulting         volume may still be lower than desired. Contact Technical         Support for information regarding this modification. 
 
 
Back to top  
VC-M System 
1. No Call Tone, but communication to and from the     handset is fine. 
Perform jumper test between terminals 1 and B. If no call         tone, the unit is defective. If call tone sounds, check wiring between B on the VC-K and         the button terminal on the VC-M panel. Make sure that the black common bus wire for all         the call switches is connected to the B terminal of the VC-M panel. If still no call tone,         switch B wire to different call button switch. If call tone is heard, then the button is         bad.  Otherwise recheck wiring.  
Refer to VC-M         Instructions. 
 
 
2. No communication from VC-K to VC-M. 
Check wiring between 1 of VC-M and 1 of VC-K.  
 
 
3. No communication from VC-M to VC-K.  
Check wiring between 2 of VC-M and 2 of VC-K. 
 
 
4. Communication is fine, but no door release. 
Check the wiring between 4 of the VC-K and 4 of the VC-M.         Check to make sure the RY-PA relay is properly attached (black leads to L+ and L-). 
Refer to VC-M         Instructions. 
 
 
Back to top  
YAZ System 
1. Specific unit is “dead”.  
Check for 24V DC at the unit. Initiate self-check mode. 
Refer to YAZ instruction       manual. 
 
2.  When two sets of handsets are     communicating and two more pick up they get a “busy” signal. 
Check for proper connection of lines 1 through 6.       (Terminals 1&2 are for channel 1, 3&4 are channel 2, 5&6 are channel 3.)       Initiate self-check mode on each handset until problem handset is found.  
Refer to YAZ instruction       manual. 
Original information can be found directly by the manufacturer at [ home ] 
 
 |