Loop Frequency:
Four frequencies (normally in
the range of 20 to 100 kHz) are dip switch selectable from the front panel.
Reset:
Changing any dip switch position
(except SW 1 & SW 2: frequency selection) will reset the detector. After
changing the Frequency selection switches, the detector will require a RESET.
Reset will clear the loop fault memory.
Sensitivity:
Vehicle detection results when
a negative change in loop inductance (-DL/L) exceeds
the sensitivity setting. Eight detection sensitivity levels are front panel
rotary switch selectable.
| Sensitivity | -DL/L |
| 0 | 1.28% |
| 1 | 0.64% |
| 2 | 0.32% |
| 3 | 0.16% |
| 4 | 0.08% |
| 5 | 0.04% |
| 6 | 0.02% |
| 7 | 0.01% |
Sensitivity Boost:
An external dip switch setting
may be turned on to increase sensitivity during the detect period. When a vehicle
enters the loop, the detector sensitivity is boosted to a higher level than
the vacant loop setting. The boosted sensitivity remains throughout the detect
period. When the vehicle leaves the loop, the sensitivity returns to the vacant
loop setting. This feature helps prevent dropouts during the passage of high
bed vehicles and is particularly useful in sliding gate situations.
Relay "A" Modes:
Two presence hold times are selectable
for Relay A with an external dip switch, "TruePresenceÔ
" and "Limited Presence". Both modes output a CALL
when a vehicle is present in the loop. TruePresenceÔ
will hold the call for as long as the vehicle is present and power is not removed
or reset applied. Limited presence will typically hold the CALL output for about
1-3 hours. The TruePresenceÔ time applies only for
normal size automobiles and trucks and for normal size loops (approx. 12 sq.
ft. to 120 sq. ft.).
Relay "B" Modes:
Two modes of operation are selectable
for Relay B with an external dip switch, Presence or Pulse. When in the presence
mode, the presence hold time is the same as Output A. When in the pulse mode,
the 250 millisecond pulse can be selected as either pulse on entry (when
a vehicle enters the loop) or pulse on exit (when a vehicle exits the
loop). Relay B is a FAIL SECURE output in the presence
and pulse modes.
CALL Delay:
A 2-second delay of Outputs A
&B can be activated by an external dip switch. Output delay is the time
the detector outputs are delayed after a vehicle first enters the loop detection
area and is indicated by the front panel detect LED flashing at 4 Hz with a
50% duty cycle. If the 2-second output delay feature is activated, the output
relays will only be turned on after 2 seconds has passed with a vehicle continuously
present in the loop detection area. If a vehicle leaves the loop detection area
during the 2-second delay interval, detection is aborted and the next vehicle
entering the loop detection area will initiate a new full 2-second delay interval.
The flashing will only occur during the 3 minute activation of the "DET"
LED.
Detect Status Indicator:
The red detect LED is steady
on while a vehicle is being detected. The detect LED will flash at a 4 Hz rate
with a 50% duty cycle while timing out the 2-Second Call Delay. NOTE: The "DET"
LED is only operational during the first 3 minutes of power or after a reset.
After the first 3 minutes of operation, the LED automatically turns off.
Loop FAIL Monitor Indicator:
If the total inductance of the
detector input network goes out of the range specified for the detector or suddenly
changes more than +/-25% the detector will enter FAIL
mode. The red FAIL LED will either begin flashing with
a 50% duty cycle once per second for an open or shorted loop condition. This
indicator condition will continue until the inductance returns to its previous
value at which time the detector output will automatically resume normal operation,
and the red FAIL LED will flash at a distinctive rate
(one flash every 5 seconds) to indicate an intermittent loop fault has occurred
and corrected. [The detector input network, consists of the loop or loops plus
the feeder cable (lead-in or home run) up to the connector on the detector].
FAIL SAFE
/ FAIL SECURE Operation:
When in the fail-safe or ON position,
Output A will output a signal when a loop fault condition exists. If the loop
fault self-corrects, Output A will assume the "No fault" output state.
When in the fail-secure or OFF position, the detector will not ouput a signal
during a loop failure condition. Note: Relay Output A & B are fail secure
on loss of power.
Self Tuning:
Automatically tunes to loop within
2 seconds after application of power or reset. 30 seconds of operation is required
before full sensitivity and presence time is reached following application of
power or a reset.
Environmental Tracking:
Fully self-compensating for environmental
changes and loop drift over the full temperature range and the entire loop inductance
range.
Loop Inductance Range:
20 to 1000 mH
with Q factor of 5 or greater.
Loop Input:
Transformer isolated. The minimum
capacitance added by the detector is 0.068 mF.
Grounded Loop Operation:
The loop isolation transformer
allows operation with poor quality loops (which may include a single point short,
or leakage, to ground).
Lightning Protection:
The detector can tolerate, without
damage, a 10 mF capacitor charged to 1,000 Volts
being discharged directly into the loop input terminals, or a 10 mF
capacitor charged to 2,000 Volts being charged between either loop terminal
and earth ground.
Relay Rating(s):
The relay contacts are rated
for 6 Amp max, 150 VDC max, 300 VAC max and 180 Watts max switched power.
Ruggedized Construction:
The enclosure is high temperature
rated lexan plastic. Printed circuit boards are double sided 2-oz copper with
plated through-holes.
Operating Temperature:
-40°
F to + 180° F. Meets or exceeds NEMA specifications.
Power(s):
10 to 14 VDC
Model BX-LP (Factory Set):
4.0 milliamps max with no vehicle in the loop zone.
35.0 milliamps max with vehicle in the loop zone and during the first 3 minutes
of power on or after a reset (LEDs are activated). Add 25.0 milliamps for dual
presence operation.
30.0 milliamps max with vehicle in the loop zone and after first 3 minutes of
power on (LEDs are de-activated). Add 25.0 milliamps for dual presence operation.
Model BX-LP-SS
(Factory Set):
4.0 milliamps max with no vehicle in the loop zone.
12.0 milliamps max with vehicle in the loop zone and during the first 3 minutes
of power on or after a reset (LEDs are activated).
4.0 milliamps max with vehicle in the loop zone and after first 3 minutes of
power on (LEDs are de-activated).
Fuse(s):
12 VDC power: Current limited.
Size:
1.75 inches (4.45 cm.) Wide x 3.00 inches (7.62 cm.) High
x 5.00 inches (12.70 cm.) Deep, including rear connector.
Weight:
Approx. 8.1 oz. (229.64 gm.).
Connector:
Rear mount 11 Pin male "Amphenol" connector (86CP11).
| BX-LP | BX-LP-SS | ||
| Pin | Function | Pin | Function |
| 1 | Power, 12 VDC (+) | 1 | Power, 12 VDC (+) |
| 2 | Power, 12 VDC (-) | 2 | Power, 12 VDC (-) |
| 3 | Output B, Normally Open | 3 | Output B, Drain |
| 4 | No Connection | 4 | No Connection |
| 5 | Output A, Common | 5 | Output A, Source |
| 6 | Output A, Normally Open | 6 | Output A, Drain |
| 7 | Loop | 7 | Loop |
| 8 | Loop | 8 | Loop |
| 9 | Output B, Common | 9 | Output B, Source |
| 10 | Output A, Normally Closed | 10 | No Connection |
| 11 | Output B, Normally Closed | 11 | No Connection |
Note: * Relay contacts are shown with power applied, loop(s) connected, and no vehicles present.
Factory Default Settings:
Sensitivity Level: Level 3
Output Configurations: Relay A =
True Presence (Infinite)
Relay B = Pulse on Entry
Sensitivity Boost: OFF
2-Second CALL Delay:
OFF
** Specifications are subject to change to reflect improvements and upgrades.